Fire Alarm System Intellignet System / Detector


 
Addressable Combustible Gas Detector - I_9602LW
 
Features
 
Available for LPG, Natural Gas and Coal Gas. (Please specify at time of order)
 
Built-in relay contacts for control of Gas Valves / Extract etc
 
Built-in sounder with 2 stage alarm
 
Manual reset and control (on/off) of relay contacts
 
Electronically addressed
 
Standalone detector version with Relay contacts for interfacing with conventional fire panels or security systems
     
    Technical Specifications
 
Operating voltage: Loop 24V , 24 v dc Power Supply
 
Operating Consumption (Power Supply): 1.5 Watt
 
Alarm Level:
  • Pre – Alarm : 12% LEL
  • Urgent Alarm : 23% LEL
 
Output :
  • K1/K2, N/O contact, 3A/220VAC, active when pre-alarm
  •  V1/V2, active output 3A/5VDC, start when full alarm
 
Operating environment:
  • Temperature:- 10 ~ + 50°C
  • Relative humidity: 95%
 
Wiring :
  • Non-polarized two-core for loop
  • Non-polarized two-core for 24VDC power supply
 
Dimension: 121 mm × 87 mm × 57 mm
 
 
     
  Addressable Combustible Gas Detector - I-9602LW

 

Addressable Combustible Gas Detector - I_9602LW